Configuring an M1 CPU with Modsoft
148
870 USE 101 00 V.2.2
Default Configuration Parameters,
Continued
Default Values
Here are the default parameters:
Parameter 2.4K Adapter 12.0K Adapter 18.0K Adapter
Coils in state RAM 1536 (0
x
) 1536 (0
x
) 1536 (0
x
)
Discrete inputs in state
RAM
512 (1
x
) 512 (1
x
) 512 (1
x
)
Input registers in state
RAM
48 (3
x
) 48 (3
x
) 48 (3
x
)
Output registers in state
RAM
1872 (4
x
) 1872 (4
x
) 1872 (4
x
)
Bytes of user memory
space available for
application logic
1678 13100 17676
Words of user memory
space for the I/O Map
32 512 32
I/O logic segments One, which will
allow you to I/O
Map the I/O points
on the local base
unit
One, which will
allow you to I/O
Map the I/O points
on the local base
unit
One, which will
allow you to I/O
Map the I/O points
on the local base
unit
Memory allocated for
configuration extension
None None None