Configuring an M1 CPU with Modsoft
870USE10110 July 2004 189
Reserving
Registers for the
TOD Clock
To reserve registers for the time-of-day clock, perform the steps in the following
table.
Next Step Setting the time (see p. 190).
Step Action
1 From the Overview menu, select Specials.
Result: The cursor moves into the Battery Coil field on the Configuration Overview
screen.
2 Push the down arrow key twice to move the cursor into the Time of Day Clock field.
3 Enter a number (the first in a series of eight) in the range of available 4xxxx
references.
Example: If you want registers 400100...400107 reserved for the TOD clock, enter
100.
4 Push <Enter>.
Result: The reference value you specified and the seven that follow it are now
reserved for TOD clock data.
A
Utility OverView I/OMap Ports Segmnts Loadable Quit
F1
TEST
F6
F7 Lev 8
PLC :
PLC Type MOMNTUM
Model M1
System Memory 2.4K
Extended Memory K
Size of Full Logic Area 01198
No. of I/O Map Words 00512
I/O : I/O Type MOMENTUM
Number of Sefments 3
IO ap Reserved Words 512
0xxxx <-> SFC None
Ranges :
0xxxx 000001 - 001536
1xxxx 100001 - 100512
3xxxx 300001 - 300048
4xxxx 400001 - 401872
4xxxx <-> SFC None
Dupl. Coils Start: 0-----
F8 OFF F9F3 F4 F5
CONFIGURATION OVERVIEW
Cfg Ext
Auto
MS-DOS Prompt - COMMAND
Specials :
Battery Coil 001536
Timer Register 4-----
Time of Day clock 4-----
Cfg. Extension Used/Size 0/ 0
Specials :
Battery Coil 001536-----
Timer Register 4-----
Time of Day clock 400100 - 400107
Cfg. Extension Used/Size 0/ 0