Configuring an M1 CPU with Concept
870USE10110 July 2004 265
Changing the Range of Discrete and Register References for an M1 CPU with
Concept
Introduction This section provides guidelines and a procedure for changing the range of discrete
(0x and 1x) and register (3x and 4x) references.
Guidelines When you change the range of discrete and register references, follow these
guidelines:
Adjust the range of discretes in increments of 16 (one word)
Adjust the range of registers in increments of 1 (one word)
The total number of register and discrete references cannot exceed the maximum
of state memory displayed at the top of the dialog.
A minimum configuration of 16 0x discretes, 16 1x discretes, one 3x register, and
one 4x register is required.
Procedure Follow the steps below to change the range of discrete and register references using
the PLC Configuration screen.
Step Action
1 From the Configure menu, select Memory Partitions OR double-click on any field
in the PLC Memory Partition section of the dialog box.
Result: The PLC Memory Partition dialog box appears, showing the maximum
memory size and the register allocation of the CPU.
2 Modify the range of your discrete and register references by changing the value in
the variable boxes, in keeping with the guidelines described above.
3 Click the <OK> button.
OK Cancel Help
PLC Memory Partition
Maximum State Memory:
State Memory Used:
State Memory Usage:
6144
2538
41%
Discretes
512
48
1872
1536
Registers
C
oils ( 0xxxx ):
D
iscretes Inputs ( 1xxxx ):
I
nput Registers ( 3xxxx ):
H
olding Registers ( 4xxxx ):