Configuring a Modbus Plus Network in Modsoft with Peer Cop
242
870USE10110 July 2004
Defining the References for the Next Node on a Modbus Supervisory Network
with Momentum Components (Using Modsoft)
Overview We now want to attach the Modsoft 2.6 programming panel to the 171 CCS 760 00
Momentum M1 CPU at Modbus Plus address 3 and create a similar Peer Cop for
this device to communicate with the supervisory PLC at Modbus Plus address 1.
In this case, we want the M1:
to send 16 words of specific output to the supervisor.
to receive the last seven words of global input from the supervisor. (Remember
that the supervisor will be transmitting a total of 10 contiguous words of global
data over the network.)
Link and Node
Settings
Make sure that the Link setting is 1 and the Node setting is 1, indicating that this CPU
will be exchanging data with the supervisory computer at address 1.
Defining Specific
Outputs
Follow the steps in the table below to define the specific output in Peer Cop.
Step Action
1 In the REFERENCE column of the SPECIFIC OUTPUT field, type the value 400024.
Push <Enter>.
Utility GoToNode AddNode OnError Quit
F1
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Timeout : 500 ms Total Links: Link Id:1
PEER COP
On Error : CLEAR USED 1 OF 2000 WORDS
REFERENCE LEN TYPE INDEXMODE
SPECIFIC INPUT -
SPECIFIC OUTPUT 400024- BIN
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
F2
Timeout
Access to Node : 1
TO ALL NODES ON LINK
GLOBAL OUTPUT -
DelNode